A 10kV box-type transformer — also referred to as a pad-mounted transformer, prefabricated substation, or unit substation — is a compact, fully integrated power distribution station that combines a power transformer, high-voltage (HV) switchgear, and low-voltage (LV) distribution equipment within a single, weatherproof steel enclosure. Designed for outdoor installation, it serves as a complete plug-and-play solution for stepping down medium-voltage power (typically 10kV) to low-voltage distribution levels (typically 0.4kV).
These units are the workhorses of modern distribution networks, widely deployed in 10/0.4kV, 50/60Hz systems with transformer rated capacities ranging from 50 kVA to 1,600 kVA. They are equally suitable for ring-network distribution architectures and as terminal power sources in radial grid configurations.
Key Advantage: Unlike traditional substations that require separate construction of transformer rooms, switchgear rooms, and civil works, box-type transformers arrive pre-assembled and pre-tested from the factory, dramatically reducing on-site installation time and civil engineering costs.
The standard 10kV box-type transformer is organized into three primary compartments, each with dedicated functional roles. The modular design ensures electrical isolation between compartments while enabling convenient access for operation and maintenance.
.png)
| Parameter | Value |
|---|---|
| Rated Voltage | 12 kV |
| Rated Current | 630 A |
| Rated Frequency | 50 / 60 Hz |
| Rated Breaking Current | 630 A |
| Thermal Stability Current (2s) | 16 kA |
| Dynamic Stability Current | 40 kA |
| Full-load Closing Time | ≤ 20 ms |
| Mechanical Life | 2,000 operations |
| 1-min Power Frequency Withstand Voltage | 42 kV |
| Lightning Impulse Withstand Voltage | 75 kV |
| Rating (kVA) | No-Load Loss S13 / S11 (W) | Load Loss S13 / S11 (W) | Impedance Voltage (%) |
|---|---|---|---|
| 50 | 100 / 130 | 910 / 870 | 4.0 |
| 100 | 150 / 200 | 1,580 / 1,500 | 4.0 |
| 200 | 240 / 340 | 2,730 / 2,600 | 4.0 |
| 315 | 340 / 480 | 3,830 / 3,650 | 4.0 |
| 500 | 480 / 680 | 5,410 / 5,150 | 4.0 |
| 630 | 570 / 810 | 6,200 / 6,200 | 4.5 |
| 800 | 700 / 980 | 7,500 / 7,500 | 4.5 |
| 1,000 | 830 / 1,150 | 10,300 / 10,300 | 4.5 |
| 1,250 | 970 / 1,360 | 12,000 / 12,000 | 4.5 |
| Parameter | Specification |
|---|---|
| HV Rated Voltage | 11, 10.5, 10, 6.3, or 6 kV |
| LV Rated Voltage | 0.4 kV (400V) |
| Connection Group | Yyn0 or Dyn11 |
| Tap Changer Range | ±5%, ±2×2.5%, or custom |
| Rated Frequency | 50 Hz / 60 Hz |
| Cooling Method | ONAN (Oil Natural Air Natural) |
The European-style design features distinct, separately compartmentalized sections for the HV switchgear, transformer, and LV switchboard. This modular "room-within-a-room" approach is the most widely adopted configuration globally.
The American-style design emphasizes compactness by integrating the transformer, HV load switch, and fuses into a single oil-immersed tank, eliminating the need for a separate HV compartment.
The integrated type merges high-voltage control and protection devices directly into the transformer enclosure, embodying a "maintenance-free" design philosophy.
| Category | Types |
|---|---|
| By Insulation Medium | Oil-immersed, Dry-type (cast resin), High-flash-point liquid |
| By Mounting | Pad-mounted (ground-level), Pole-mounted, Indoor |
| By Configuration | Combination device type, One-body type |
| By Network Role | Terminal type, Ring-network type |
Get a customized solution tailored to your project requirements — fast quote, factory-direct pricing, and global shipping support.